Precision PCB Fabrication, High-Frequency PCB, High-Speed PCB, Standard PCB, Multilayer PCB and PCB Assembly.
The most reliable PCB & PCBA custom service factory.
PCB News

PCB News - What are the temperature and humidity requirements of SMT factory workshop?

PCB News

PCB News - What are the temperature and humidity requirements of SMT factory workshop?

What are the temperature and humidity requirements of SMT factory workshop?

2021-10-04
View:830
Author:Frank

What are the temperature and humidity requirements and management methods of the SMT factory workshop?
The Internet era has broken the traditional marketing model, and a large number of resources have been gathered together to the greatest extent through the Internet, which has also accelerated the development speed of FPC flexible circuit boards, and then as the development speed accelerates, environmental problems will continue to appear in PCB factories. In front of him. However, with the development of the Internet, environmental protection and environmental informatization have also been developed by leaps and bounds. Environmental information data centers and green electronic procurement are gradually being applied to the actual production and operation fields.
The SMT factory workshop has clear requirements for temperature and humidity. The editor and industry personnel jointly worked out the workshop temperature and humidity standard parameters, as well as management standards. It is posted now for reference by SMT counterparts.

1. Requirements of temperature and relative humidity in SMT workshop:
Temperature: 24±2 degree Celsius

Humidity: 60±10%RH

2. Temperature and humidity testing equipment:
PTH-A16 precision temperature and humidity inspection instrument

pcb

1. Using Pt100 platinum resistance as the temperature sensor to ensure the accuracy and stability of the temperature measurement;

2. The relative humidity is measured by the ventilated dry-wet bulb method, which avoids the influence of wind speed on humidity measurement;

3. Resolution: temperature: 0.01 degree Celsius; humidity: 0.01%RH;

4. Overall error (electrical measurement + sensor): temperature: ±(0.1~0.2) degree Celsius; humidity: ±1.5%RH.

3. Relevant regulations for environmental control in SMT workshop:
1. The parameter values are set by the SMT engineering department according to product requirements and seasonal changes.

2. The placement of the daily thermometer and hygrometer: an electronic pointer type dry and wet bulb thermometer and hygrometer are used, placed in the densest area of the machine, so that the most significant temperature and humidity changes can be collected.

3. The recording period of the thermometer and hygrometer is set to 7 days, and the recording table is changed every Monday at 7:30 in the morning. The replaced record sheet is stored in a specific folder, and the retention period is at least 1 year. A new record sheet can be applied to the Engineering Department. The start date must be stated on the form. When the record sheet is replaced, the record start time must be the same as the replacement form.

4. The switch of the indoor air-conditioning system and the humidity control system (humidifier, humidifier) switch are handed over to the relevant personnel of the Public Works Department, and personnel from other departments are not allowed to use them without authorization.

5. The exhaust port of reflow soldering must be cleaned once a month to prevent excessive water accumulation. 6. Turn off the air outlet switch of the air-conditioning system on holidays and holidays, and ask the Public Works Department not to turn off the air-conditioning system air outlet switch to prevent condensation on the inner wall of the machine.

4. Requirements for daily inspection of temperature and humidity
1. The inspection work is in charge of the SMT Engineering Section.

2. The number of inspections is four times a day, divided into four time periods: 7:00~~12:00; 12:00~~19:00; 19:00~~2:00; 2:00~~7 :00. (Twice each for day shift and night shift)

3. The results of each inspection must be recorded in the prescribed form, and the name of the inspector must be signed.

4. If the temperature and humidity value on the temperature and humidity record sheet is within the required range, write "OK" in the two columns of the/humidity condition> in the attached table. If it is found that the value is not within the required range, then Write "NG" and the corresponding temperature and humidity exceeding value in the corresponding column in the attached table, and notify the person in charge of the SMT engineering department immediately.

5. The person in charge of the SMT engineering section should immediately notify the person in charge of the production section after receiving the notice, and may request to stop the machine if necessary, and notify the engineering section to check the air conditioning system and humidity control system.

6. After the temperature and humidity return to the required range, the person in charge of the SMT engineering department should immediately notify the production department to resume production.
7. It is not necessary to record the temperature and humidity on rest days or holidays.
Our factory is located in China. For decades, Shenzhen has been known as the world's electronics R&D and manufacturing center. Our factory and website are approved by the Chinese government, so you can skip the middlemen and buy products on our website with confidence. Because we are a direct factory, this is the reason why 100% of our old customers continue to purchase on iPCB.